TCMK5265 Addressable I/O Module
non-polarized two bus,ultra-low power consumption,no need to add DC24V power supply
passive outputvv input and output have isolating loop to effectively filter out external interference
1.Fix the base with two tapping screws,and then connect loop to terminals(polarity-insensitive).After thebase is fixed firmly,rotate the bottom of detector and base clockwise,and then the detector will be fitted tothe base.
2.Wiring instructions:RVS twisted pair with cross-sectional area≥1.0mm2 should be selected for the secondbus of the detector,which should be laid through metal pipe or flame retardant pipe.The length of theconnecting wire should be limited to the single bus resistance≤20Q,otherwise the wire diameter should beincreased.
Rated operating voltage Loop:24V(14V~28V);
Operating current Monitoring current: ≤ 0.2mA start current: ≤ 0.5mA
Operating Environment Temperature:-10℃~+55℃;
Relative Humidity:≤95% non-condensing
Input supervisory external loop Open circuit occurs when normally open terminal supervising
externalloop (short circuit is an action signal), the module will
send a fault signalto the control panel.
Material and color ABS;Porcelain white
Output supervisory external loop Short circuit or open circuit on the output loop occurs,
the module will send a fault signal to the contaol panel
Weight 147g
Mounting hole distance 60mm
Dimension(L×W×H) 86mm×38mm×86mm(with base)