Residual Current Transformer
TC-DH01B-J325
Through-line aperture: 325 × 60mm
main circuit rated operating current: less than 1000A
Dimensions: 445mm × 220mm × 60mm
Connected to the monitoring device JB-DH-TC5600 with a non-polar two buses, while achieving communication and power supply functions
The address code is electronically encoded and can be written in advance by the electronic encoder. The engineering debugging is simple and reliable
The microprocessor monitors the operation and transmits the status of the module to the monitoring device in both normal and alarm modes
Wire system: non-polar connection to the signal bus of the monitoring device
Residual current detector Specification:
1. Operating Voltage: Pulse voltage of circuit loop: Loop 24V Available range:
16V~30V
2. Operating current: Standby current≤0.4mA Alarming current≤0.7mA
3. Rated alarming current: 200mA~1000mA, step-size 1mA
4. Encoding mode: electrical addressable mode. It takes one site on the loop. And an addressable code could be any in the range of 1~255.
5. Cabling: connecting with the monitoring devices through signal nonpolar two-line loop.
6. Aperture of wires: 325mm×60mm
7. Rated operating current of main loop: less than 1000A.
8. Rated frequency of wires: 50Hz/60Hz
9. Ambient environment: Temperature: -10℃~+55℃ Relative humidity≤95%, non-condensing
10. Dimension: 445mm×220mm×60mm
11. Enclosure material: ABS plastic
12. Ingress Protection Rating: IP30
13. Weight: about 8kg
© Copyright 2018~2025 by vedard.com